Reliability: Specification of MTBF and service lifetime for PULS power supplies

In practice, the terms ‘MTBF’ and ‘service life’ are often mixed up or used interchangeably. However, these refer to different processes and both values are needed to describe reliability. What they have in common is that higher temperatures make the values much worse.

MTBF

Where does this value come from ?

The MTBF (Mean Time Between Failure) specifies how often a unit fails as a statistical average. Even if all parties strive to keep the number of failures as low as possible, it is unavoidable that a technical product fails with a certain level of probability. The frequency of the failures is represented by the symbol for failure rate λ (Lambda). The MTBF is the reciprocal value of λ. λ specifies the number of failures per unit hour.

In practice, specifications in MTBF are more common, presumably because the failure rate λ is given in 1/hour, and is a smaller value (as is the „failure in time“ specification; 1 fit = 10-9 failures per hour), whereas the MTBF uses the unit of hours. It is important to understand that the failure rate/MTBF relates to statistical failures that apply from the first operating hour. Early failures are not taken into account as the manufacturer should exclude these occurring at the customer‘s site. Wear effects do not play a role here either, as it starts from the phase in which no age-related failures should occur. Higher temperatures accelerate the processes, low temperatures are very important for a low failure rate or high MTBF.

Example calculation of the MTBF values

The failure rate expresses how many failures are to be expected when a certain number of units are operated for a specific period. This is the specification of interest in practice. An example: We take 1,000 units and operate them for 2,000 hours. This results in 2 million unit hours. If we observe 4 failures in this period, the failure rate is 4 failures / 2 million unit hours = 2 x 10-6 per hour or 2 ppm per hour. The MTBF as the reciprocal value of 2 x 10-6 per hour gives 500,000h, which is clearer.

You can look at it like this: If you operate 1,000 units for 2,000 hours, corresponding to 2 million unit hours, and the MTBF
is 500,000h, we can expect four failures (2 million / 500k = 4). A simple working hypothesis could also be that 500,000 units are operated simultaneously, of which each has an MTBF of 500,000h: one unit would then fail every hour.

Lifespan

The lifespan does not relate to statistical failures during the normal operating time but instead refers to the time after which the components are no longer usable due to wear and tear. This specifies after how many years a power supply can no longer perform its specified service.

What determines the service life?

The most relevant components affecting the service lifetime in a power supply are the electrolytic capacitors. They contain liquid
electrolyte that during the course of time is diffused by the component seal. The end of the service life is defined by the manufacturer when parameters such as capacity and internal resistance have degenerated by a specific amount from the start value. The service lifetime is therefore dependent on the type of electrolytic capacitor and also on its operating temperature. Every increase of 10°C reduces the service life by a factor of 2.

Comparison of the reliability values for the CP10 with 24V/10A under various conditions

Lifespan

5 A 25°C 230V 499.000h
10 A 25°C 230V 338.000h
10 A 25°C 120V 211.000h
5A 40°C 230V 176.000h
10A 40°C 230V 120.000h
10A 40°C 120V 75.000h

MTBF:

10 A 25°C 230V SN 29500: 1.185.000h MIL HDBK 217F: 381.000h

Comparison between the MTBF and the lifespan 

A clear comparison of the statistical failure rate MTBF and the expiry of the service life in a range of applications is given in figure 3.

Two examples 

 

  1. In a rocket, a lifespan of 5 to 10 minutes is sufficient since she has done her job and crashes. With the various components that such a rocket contains, and the potential damage that can be caused by non-functionality, the possibility of malfunction during these 10 minutes should be extremely low, which means a very high MTBF.
  2. An opposite example is an amplifier in a submarine cable. It must last 40 years and longer because it is difficult to replace. On the other hand, it is not that complex and a poorer MTBF is acceptable in compensation with a longer life.

Multiple calculation method, but only one correct

For high quality industrial power supplies, both the MTBF and the service lifetime are important. During the normal duration of use, as few failures as possible should interrupt operation and the usability of the machine should be achieved over many years without changing components. Since the introduction of the DIMENSION product range, PULS has been a pioneer in specifying the values for MTBF and service life in its data sheets. Considerable value is set on ensuring that the definitions are clearly specified.

With the MTBF in particular, there are many ways to calculate the figure and depending on the calculation method and the definition of the operating conditions, the results are very different. The simplest method is the „parts count“. Here only the number of components is counted and multiplied by a mean failure rate to calculate to the failure rate of the overall equipment. This is an over-simplification. It is more precise, more complicated and therefore unpopular with developers to consider each individual component in the power supply (which can be hundreds) to determine the electrical stress via calculation and the thermal stress via measurement. These values then produce a program on the failure rate for the component under this stress condition and the total of the individual failure rates of the components gives the total failure rate/ MTBF of the device.

Different standards for MTBF values

There are existing various standards for the failure rate of the components. The MIL Handbook 217F has widespread international acceptance, but according to PULS‘ experience, the values it uses for failure rates are too conservative. The values in Siemens standard SN 29500 that are based on a broad range of industrial experience are more realistic. The calculation method is defined in the IEC 61709. When assessing an MTBF value it is therefore always important to know both the underlying data used as well as the operating conditions (stress factors) of the equipment. MTBF figures without this information are worthless.

As temperature has a significant influence, a precise definition is important here. The key issues are the temperature of the individual components and these are dependent on the ambient temperature and selfheating. The self-heating results from the losses in the power supply and varies with the load and the input voltage. The ambient temperature alone has a considerable influence and as a result PULS specifies the MTBF at +25°C to facilitate a comparison with other manufacturers, and at +40°C because this is a more realistic operating condition as full load is assumed at all times. Even at a standardized full load, the bandwidth – e. g. for a CP10 – ranges from 250,000h (MIL, 100Vac, +40°C) to 1 185 000h (SN 29500, 230Vac, +25°C), in other words a difference of a factor of 4.7.

How does PULS calculate the service life?

The data specified by the manufacturers of the electrolytic capacitors is used to calculate the lifetime. These are minimum values as the manufacturers guarantee that at the specified load, the capacity has decreased by no more than 20% from the baseline and the internal resistance is still below double the specified value. PULS determines the temperature stress of all electrolytic capacitors under different operating conditions and then calculates the service lifetime based on the manufacturer specifications. In practice this provides a reserve because a power supply can still function with these impairments but as there are no further reliable specifications available, this gives the user a good basis for comparison.

PULS attaches great importance to MTBF and the service life of its products

PULS makes the reliability of its products a very high priority. As a consequence, the data for MTBF and service lifetime is described in great detail in the data sheets for every product and is specified precisely for many operating conditions. In addition, there is an in-house guideline at PULS defining that for every product in the DIMENSION range a minimum service life of 50,000h has to be accomplished at full load, nominal mains voltage 120V/230V and an ambient temperature of +40°C in accordance with the method described above. This requires an additional loop in the development process, but the user has the advantage that he can take any product from the range and rely on specified and uniform minimum values. When looking at the values for reliability in particular, significant differences in comparison to other power supplies can be seen clearly.